![]() Title:Use of Grid-Forming Inverters to Mitigate Subsynchronous Resonance Authors:Amelia Mendes, Luiza Buscariolli, Victoria Alejandra Herrera, Ahda Pavani, Maurício Salles and Luís Felipe Normandia Lourenço Conference:SBAI-SBSE-2025 Tags:compensação série, DFIG, estabilidade de redes, inversor formador de rede (GFM) and ressonância subsíncrona Abstract: The increase in inverter based resources (IBR) leads to stability problems. The literature shows that wind farms with doubly-fed induction generators (DFIG) have negative resistance at certain frequencies and, when connected to grids with series compensation, they reduce the system's damping, causing subsynchronous oscillations to appear. The use of grid-forming inverters (GFM) is a possible mitigation alternative. This work shows, through frequency scanning, that the GFM inverter increases system damping and in fact serves as a mitigation measure for subsynchronous oscillation phenomena. Use of Grid-Forming Inverters to Mitigate Subsynchronous Resonance ![]() Use of Grid-Forming Inverters to Mitigate Subsynchronous Resonance | ||||